For system voltages of 0 to 150 volts to ground, the minimum depth of working space is ____ ft under all three working space conditions.


A) 1
B) 2
C) 3
D) 4

E) A) and B)
F) A) and C)

Correct Answer

verifed

verified

In general, panelboards are constructed so the ____ run vertically for nearly the height of the panelboard.


A) branch circuits
B) receptacles
C) cross feed buses
D) main feed busbars

E) B) and C)
F) A) and C)

Correct Answer

verifed

verified

All working spaces must allow for the opening of equipment doors and hinged panels to at least a ____ degree position.


A) 45
B) 60
C) 90
D) 135

E) A) and B)
F) A) and C)

Correct Answer

verifed

verified

C

Panelboard ratings are determined by the ____ capacity of the internal main bus.


A) voltage-carrying
B) current-carrying
C) resistance
D) impedance

E) A) and D)
F) None of the above

Correct Answer

verifed

verified

The reasoning for identifying the system voltage(s) and phases is ____.


A) safety
B) registration
C) precision
D) scheduling

E) All of the above
F) B) and D)

Correct Answer

verifed

verified

The circuit directory gives the ____ for each circuit in a wording that would be clear for "nonelectrical" people to decipher and identify the circuit number for luminaires, receptacles, appliances, or equipment.


A) ampacity
B) current limit
C) purpose of use
D) panelboard rating

E) None of the above
F) A) and B)

Correct Answer

verifed

verified

​If more than one system voltage is used for premises wiring, how should panelboards be marked?

Correct Answer

verifed

verified


NEC 210.5(C)requires that where more...

View Answer

What are the three conditions related to live parts and working space?

Correct Answer

verifed

verified

Condition 1-Exposed live parts on one si...

View Answer

Working space height is required to not be less than ____ ft.


A) 5.5
B) 6.5
C) 7.5
D) 8.5

E) B) and C)
F) A) and D)

Correct Answer

verifed

verified

Often a feeder serves two or more panelboards, in which case either a(n) ____ or wireway is installed or the feeder connects to the first panelboard and then is extended to the others.


A) ell
B) tee
C) junction box
D) fusebox

E) B) and C)
F) C) and D)

Correct Answer

verifed

verified

What are the requirements for panelboard cabinet sizing?

Correct Answer

verifed

verified

If there are special requirements for using the wiring gutters in a panelboard, the physical size of the cabinet is required to be sufficient to accommodate those requirements. Often a feeder serves two or more panelboards, in which case either a junction box or wireway is installed or the feeder connects to the first panelboard and then is extended to the others. In some cases, double lugs are installed for the phase conductors and neutral, if used. Other designs have feed-through lugs with the supply-side feeder conductors connected to the line terminals of the first panelboard and conductors of the same size connected from the load terminals of the first panelboard to the line terminals of the second panelboard. Both methods require the installation of additional feeder conductors. The cabinet must have sufficient gutter width for bending these conductors and for the required splices if splices are made.

The feeder overcurrent protection is sized for the ____ of the feeder conductor.


A) dimensions
B) ampacity
C) resistance
D) voltage drop

E) None of the above
F) B) and C)

Correct Answer

verifed

verified

Unused openings in panelboards and switches should be ____.


A) marked as a pinch point
B) marked as a hazard point
C) available for expansion
D) closed

E) A) and D)
F) B) and D)

Correct Answer

verifed

verified

NEC 408.36(A) stipulates that if the panelboard contains snap switches with a rating of ____ amperes or less, the panelboard overcurrent protection is not permitted to exceed 200 amperes.


A) 15
B) 30
C) 50
D) 100

E) A) and D)
F) A) and C)

Correct Answer

verifed

verified

For electrical equipment not considered large, at least ____  entrance(s) of sufficient area is required to provide access to and egress from the working space.


A) one
B) two
C) three
D) four

E) All of the above
F) B) and D)

Correct Answer

verifed

verified

A

What are the requirements for preparing a circuit directory?

Correct Answer

verifed

verified

NEC 408.4 is very clear as to its requi...

View Answer

Most large commercial buildings use two voltages: 480Y/277 volts and ____/120 volts.


A) 480 delta
B) 365Y
C) 208 delta
D) 208Y

E) A) and B)
F) A) and C)

Correct Answer

verifed

verified

Separate feeders are to be run from the main service equipment to each of the areas of the commercial building. Each feeder will terminate in a ____, which generally will be installed in the area to be served.


A) panelboard
B) switchboard
C) fusebox
D) lightboard

E) C) and D)
F) All of the above

Correct Answer

verifed

verified

Conductors for 480Y/277-volt systems are generally brown, orange, ____ for the ungrounded conductors and gray for the grounded conductor..


A) green
B) black
C) yellow
D) blue

E) A) and B)
F) None of the above

Correct Answer

verifed

verified

What is the difference between past and current usages of the term panelboard?

Correct Answer

verifed

verified

In the past, panelboards were defined tw...